Gen Set Ratings for TLIGLC145NL-C
Model Natural Gas 12:1 LP Gas 10:1 Voltage
Hi-Wye
Voltage
Low-Wye
Voltage Delta Number of Leads Phase Hz Power Factor
kW Rating Standby kW Rating Prime kW Rating Standby kW Rating Prime
TLIGLC145N/L-CA 145 130 135 125 480/277 240/139 N/A 12 3 60 0.8
TLIGLC145N/L-CA 145 130 135 125 440/254 220/127 N/A 12 3 60 0.8
TLIGLC145N/L-CA 145 130 135 125 416/240 208/120 240/120 12 3 60 0.8
TLIGLC145N/L-CB 145 130 135 125 380/220 N/A N/A 12 3 60 0.8
TLIGLC145N/L-CE 145 130 135 125 N/A N/A 240/120 4 1 60 1.0
TLIGLC145N/L-CH 145 130 135 125 600/347 N/A N/A 12 3 60 0.8
TLIGLC145N/L-CXA 125 110 115 105 380/220 N/A 220/110 12 3 50 0.8
NOTES:
1) For ratings and voltages not listed above, consult Tele-Lite.
2) Standby ratings do not have an overload capability but can be used for the duration of the utility failure per ISO-3046, DIN 6271 and BS 5514.
3) Prime (Unlimited Running Time) ratings are continuous per DIN 6271 and ISO-3046 with 10% overload capacity.
4) Base load (continuous) ratings are continuous per DIN 6271, BS 5514 and ISO-8528 with no sustained overload capacity. Consult Tele-Lite for base load ratings.
5) Altitude derate is 4% for each 1000 feet over 3000.
6) Temperature derate is 1% for 10°F over 100°F ambient.