Model TLGLC30 Natural Gas LP Gas
150°C Rise Standby Rating 105°C Rise Prime Rating 150°C Rise Standby Rating 105°C Rise Prime Rating
Generator Voltage Phase Hz kW/kVa Amps kW/kVa Amps kW/kVa Amps kW/kVa Amps
UCI224C 120/208 3 60 30/38 104 27/34 94 30/38 104 27/34 94
127/220 3 60 30/38 98 27/34 89 30/38 98 27/34 89
120/240 3 60 30/38 90 27/34 81 30/38 90 27/34 81
139/240 3 60 30/38 90 27/34 81 30/38 90 27/34 81
220/380 3 60 30/38 57 27/34 51 30/38 57 27/34 51
277/480 3 60 30/38 45 27/34 41 30/38 45 27/34 41
BCI184G 120/240 1 60 30/30 250/125 27/27 225/112 30/30 250/125 27/27 225/112
NOTES:
1) For ratings and voltages not listed above, consult Tele-Lite.
2) Standby ratings do not have an overload capability but can be used for the duration of the utility failure per ISO-3046, DIN 6271 and BS 5514.
3) Prime (Unlimited Running Time) ratings are continuous per DIN 6271 and ISO-3046 with 10% overload capacity.
4) Base load (continuous) ratings are continuous per DIN 6271, BS 5514 and ISO-8528 with no sustained overload capacity. Consult Tele-Lite for base load ratings.
5) Altitude derate is 4% for each 1000 feet over 5000.
6) Temperature derate is 1% for 10°F over 100°F ambient.