Model TLGLC30 | Natural Gas | LP Gas | |||||||||
150°C Rise Standby Rating | 105°C Rise Prime Rating | 150°C Rise Standby Rating | 105°C Rise Prime Rating | ||||||||
Generator | Voltage | Phase | Hz | kW/kVa | Amps | kW/kVa | Amps | kW/kVa | Amps | kW/kVa | Amps |
UCI224C | 120/208 | 3 | 60 | 30/38 | 104 | 27/34 | 94 | 30/38 | 104 | 27/34 | 94 |
127/220 | 3 | 60 | 30/38 | 98 | 27/34 | 89 | 30/38 | 98 | 27/34 | 89 | |
120/240 | 3 | 60 | 30/38 | 90 | 27/34 | 81 | 30/38 | 90 | 27/34 | 81 | |
139/240 | 3 | 60 | 30/38 | 90 | 27/34 | 81 | 30/38 | 90 | 27/34 | 81 | |
220/380 | 3 | 60 | 30/38 | 57 | 27/34 | 51 | 30/38 | 57 | 27/34 | 51 | |
277/480 | 3 | 60 | 30/38 | 45 | 27/34 | 41 | 30/38 | 45 | 27/34 | 41 | |
BCI184G | 120/240 | 1 | 60 | 30/30 | 250/125 | 27/27 | 225/112 | 30/30 | 250/125 | 27/27 | 225/112 |
NOTES: 1) For ratings and voltages not listed above, consult Tele-Lite. 2) Standby ratings do not have an overload capability but can be used for the duration of the utility failure per ISO-3046, DIN 6271 and BS 5514. 3) Prime (Unlimited Running Time) ratings are continuous per DIN 6271 and ISO-3046 with 10% overload capacity. 4) Base load (continuous) ratings are continuous per DIN 6271, BS 5514 and ISO-8528 with no sustained overload capacity. Consult Tele-Lite for base load ratings. 5) Altitude derate is 4% for each 1000 feet over 5000. 6) Temperature derate is 1% for 10°F over 100°F ambient. |