| Alternator Performance Data for TLIGLC880N-C |
| Model | TLIGLC880N-CA | TLIGLC880N-CB | TLIGLC880N-CC | TLIGLC880N-CH |
| Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/41° C | 150/42° C | 150/43° C |
| Generator Model Number | HCI634H | HCI634J | HCI634K | HCI634J |
| Generator kW at 130/105/80°C/40°C Ambient (480V, 60Hz) | 850/770/680 | 1040/950/828 | 1150/1050/900 | 1040/950/828 |
| SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 2300 | 2600 | 3200 | 2600 |
| Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
| Subtransient Reactance at Voltage Listed | 16.00% | 16.00% | 15.00% | 16.00% |
| Line - Line Harmonic Maximum Total | 3.50% | 3.50% | 3.50% | 3.50% |