Alternator Performance Data for TLIGLC575NL-C |
Model | TLIGLC575N/L-CA | TLIGLC575N/L-CB | TLIGLC575N/L-CC | TLIGLC575N/L-CH |
Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C | 150/40° C |
Generator Model Number | HCI544E | HCI544F | HCI634G | HCI544E |
Generator kW at 130/105/80°C/40°C Ambient (480V, 60Hz) | 600/540/475 | 620/575/506 | 740/675/588 | 600/540/475 |
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 1500 | 1840 | 2000 | 1500 |
Maximum SKVA at 90% Sustained Voltage Dip | 1779 | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
Subtransient Reactance at Voltage Listed | 10.00% | 9.00% | 18.00% | 10.00% |
Line - Line Harmonic Maximum Total | 3.50% | 3.50% | 3.50% | 3.50% |