Alternator Performance Data for TLIGLC575NL-C
ModelTLIGLC575N/L-CATLIGLC575N/L-CBTLIGLC575N/L-CCTLIGLC575N/L-CH
Temperature Rise By Resistance (Stand-By)150/40° C150/40° C150/40° C150/40° C
Generator Model NumberHCI544EHCI544FHCI634GHCI544E
Generator kW at 130/105/80°C/40°C Ambient (480V, 60Hz)600/540/475620/575/506740/675/588600/540/475
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz1500184020001500
Maximum SKVA at 90% Sustained Voltage Dip1779Consult Tele-LiteConsult Tele-LiteConsult Tele-Lite
Subtransient Reactance at Voltage Listed10.00%9.00%18.00%10.00%
Line - Line Harmonic Maximum Total3.50%3.50%3.50%3.50%