Alternator Performance Data for TLIGLC500N-C
ModelTLIGLC500N-CATLIGLC500N-CBTLIGLC500N-CCTLIGLC500N-CH
Temperature Rise By Resistance (Stand-By)150/40° C150/40° C150/40° C150/40° C
Generator Model NumberHCI544DHCI544EHCI544FHCI544D
Generator kW at 130/105/80°C/40°C Ambient (480V, 60Hz)475/430/376600/540/475620/575/506475/430/376
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz1300150018401300
Maximum SKVA at 90% Sustained Voltage DipConsult Tele-LiteConsult Tele-LiteConsult Tele-LiteConsult Tele-Lite
Subtransient Reactance at Voltage Listed10.00%10.00%9.00%10.00%
Line - Line Harmonic Maximum Total3.50%3.50%3.50%3.50%