Alternator Performance Data for TLIGLC350NL-C |
Model | TLIGLC350N/L-CA | TLIGLC350N/L-CB | TLIGLC350N/L-CH |
Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C |
Generator Model Number | HCI444F | HCI544C | HCI444F |
Generator kW at 130/105/80°C/40°C Ambient (480V, 60Hz) | 365/336/292 | 440/400/352 | 365/336/292 |
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 1040 | 1200 | 1040 |
Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
Subtransient Reactance at Voltage Listed | 10.00% | 11.00% | 10.00% |
Line - Line Harmonic Maximum Total | 3.50% | 3.50% | 3.50% |