Alternator Performance Data for TLIGLC325NL-C
ModelTLIGLC325N/L-CATLIGLC325N/L-CBTLIGLC325N/L-CCTLIGLC325N/L-CH
Temperature Rise By Resistance (Stand-By)150/40° C150/40° C150/40° C150/40° C
Generator Model NumberHCI444EHCI444FHCI544CHCI444E
Generator kW at 130/105/80°C/40°C Ambient (480V, 60Hz)315/290/255365/336/292440/400/352315/290/255
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz85010401200850
Maximum SKVA at 90% Sustained Voltage DipConsult Tele-LiteConsult Tele-LiteConsult Tele-LiteConsult Tele-Lite
Subtransient Reactance at Voltage Listed12.00%10.00%11.00%12.00%
Line - Line Harmonic Maximum Total3.50%3.50%3.50%3.50%