| Alternator Performance Data for TLIGLC250NL-C |
| Model | TLIGLC250N/L-CB | TLIGLC250N/L-CC | TLIGLC250N/L-CD | TLIGLC250N/L-CH |
| Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C | 150/40° C |
| Generator Model Number | HCI444C | HCI444D | HCI444E | HCI444C |
| Generator kW at 130/105/80°C/40°C Ambient (480V, 60Hz) | 235/216/188 | 280/252/216 | 315/290/255 | 235/216/188 |
| SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 640 | 720 | 850 | 640 |
| Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
| Subtransient Reactance at Voltage Listed | 14.00% | 13.00% | 12.00% | 14.00% |
| Line - Line Harmonic Maximum Total | 3.50% | 3.50% | 3.50% | 3.50% |