Alternator Performance Data for TLIGLC215NL-C
ModelTLIGLC215N/L-CATLIGLC215N/L-CBTLIGLC215N/L-CCTLIGLC215N/L-CH
Temperature Rise By Resistance (Stand-By)150/40° C150/40° C150/40° C150/40° C
Generator Model NumberUCI274HUCD274JHCI444DHCI444E
Generator kW at 130/105/80°C/40°C Ambient (480V, 60Hz)204/188/163240/220/194280/252/216235/216/188
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz600680720640
Maximum SKVA at 90% Sustained Voltage DipConsult Tele-LiteConsult Tele-LiteConsult Tele-LiteConsult Tele-Lite
Subtransient Reactance at Voltage Listed11.00%8.00%13.00%14.00%
Line - Line Harmonic Maximum Total3.50%3.50%3.50%3.50%