Alternator Performance Data for TLIGLC185NL-C
ModelTLIGLC185N/L-CBTLIGLC185N/L-CCTLIGLC185N/L-CFTLIGLC185N/L-CH
Temperature Rise By Resistance (Stand-By)150/40° C150/40° C150/40° C150/40° C
Generator Model NumberUCI274HUCD274JHCI444EUCI274H
Generator kW at 130/105/80°C/40°C Ambient (480V, 60Hz)204/188/163240/220/194315/290/255204/188/163
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz600680850600
Maximum SKVA at 90% Sustained Voltage DipConsult Tele-LiteConsult Tele-LiteConsult Tele-LiteConsult Tele-Lite
Subtransient Reactance at Voltage Listed11.00%8.00%12.00%11.00%
Line - Line Harmonic Maximum Total3.50%3.50%3.50%3.50%