Alternator Performance Data for TLIGLC150NL-C
ModelTLIGLC150N/L-CATLIGLC150N/L-CBTLIGLC150N/L-CCTLIGLC150N/L-CD
Temperature Rise By Resistance (Stand-By)150/40° C150/40° C150/40° C150/40° C
Generator Model NumberUCI274FUCI274GUCI274HUCD274J
Generator kW at 130/105/80°C/40°C Ambient (480V, 60Hz)165/150/128180/165/140204/188/163240/220/194
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz420510600680
Maximum SKVA at 90% Sustained Voltage DipConsult Tele-LiteConsult Tele-LiteConsult Tele-LiteConsult Tele-Lite
Subtransient Reactance at Voltage Listed12.00%12.00%11.00%8.00%
Line - Line Harmonic Maximum Total3.50%3.50%3.50%3.50%