Alternator Performance Data for TLIGLC145NL-C |
Model | TLIGLC145N/L-CA | TLIGLC145N/L-CB | TLIGLC145N/L-CD | TLIGLC145N/L-CH |
Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C | 150/40° C |
Generator Model Number | UCI274F | UCI274G | UCD274J | UCI274F |
Generator kW at 130/105/80°C/40°C Ambient (480V, 60Hz) | 165/150/128 | 180/165/140 | 240/220/194 | 165/150/128 |
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 420 | 510 | 680 | 420 |
Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
Subtransient Reactance at Voltage Listed | 12.00% | 12.00% | 8.00% | 12.00% |
Line - Line Harmonic Maximum Total | 3.50% | 3.50% | 3.50% | 3.50% |