Alternator Performance Data for TLIGLC145NL-C
ModelTLIGLC145N/L-CATLIGLC145N/L-CBTLIGLC145N/L-CDTLIGLC145N/L-CH
Temperature Rise By Resistance (Stand-By)150/40° C150/40° C150/40° C150/40° C
Generator Model NumberUCI274FUCI274GUCD274JUCI274F
Generator kW at 130/105/80°C/40°C Ambient (480V, 60Hz)165/150/128180/165/140240/220/194165/150/128
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz420510680420
Maximum SKVA at 90% Sustained Voltage DipConsult Tele-LiteConsult Tele-LiteConsult Tele-LiteConsult Tele-Lite
Subtransient Reactance at Voltage Listed12.00%12.00%8.00%12.00%
Line - Line Harmonic Maximum Total3.50%3.50%3.50%3.50%