Alternator Performance Data for TLIGLC125NL-C
ModelTLIGLC125N/L-CATLIGLC125N/L-CBTLIGLC125N/L-CDTLIGLC125N/L-CH
Temperature Rise By Resistance (Stand-By)150/40° C150/40° C150/40° C150/40° C
Generator Model NumberUCI274EUCI274FUCI274HUCI274E
Generator kW at 130/105/80°C/40°C Ambient (480V, 60Hz)143/128/110165/150/128204/188/163143/128/110
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz380420590380
Maximum SKVA at 90% Sustained Voltage DipConsult Tele-LiteConsult Tele-LiteConsult Tele-LiteConsult Tele-Lite
Subtransient Reactance at Voltage Listed14.00%12.00%11.00%14.00%
Line - Line Harmonic Maximum Total3.50%3.50%3.50%3.50%