| Alternator Performance Data for TLIDLC800-M |
| Model | TLIDLC800-MA | TLIDLC800-MB | TLIDLC800-MC | TLIDLC800-MD |
| Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C | 150/40° C |
| Generator Model Number | HCI634G | HCI634H | HCI634J | HCI634G |
| Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz) | 800/730/632 | 900/820/720 | 1040/950/828 | 800/730/632 |
| SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 2400 | 2700 | 3000 | 2400 |
| Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
| Subtransient Reactance at Voltage Listed | 18.00% | 16.00% | 16.00% | 18.00% |
| Line - Line Harmonic Maximum Total | 5.00% | 5.00% | 5.00% | 5.00% |