| Alternator Performance Data for TLIDLC80-JD |
| Model | TLIDLC80-JDB | TLIDLC80-JDC | TLIDLC80-JDF | TLIDLC80-JDH |
| Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C | 150/40° C |
| Generator Model Number | UCI224G | UCI274C | UCI224G | UCI224G |
| Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz) | 83/76/66 | 100/90/78 | 83/76/66 | 83/76/66 |
| SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 310 | 345 | 310 | 310 |
| Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
| Subtransient Reactance at Voltage Listed | 11.00% | 13.00% | 11.00% | 11.00% |
| Line - Line Harmonic Maximum Total | 5.00% | 5.00% | 5.00% | 5.00% |