Alternator Performance Data for TLIDLC750-M |
Model | TLIDLC750-MA | TLIDLC750-MB | TLIDLC750-MH |
Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C |
Generator Model Number | HCI634G | HCI634H | HCI634G |
Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz) | 800/730/632 | 900/820/720 | 800/730/632 |
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 2400 | 2700 | 2400 |
Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
Subtransient Reactance at Voltage Listed | 18.00% | 16.00% | 16.00% |
Line - Line Harmonic Maximum Total | 5.00% | 5.00% | 5.00% |