Alternator Performance Data for TLIDLC70-JD |
Model | TLIDLC70-JDB | TLIDLC70-JDC | TLIDLC70-JDE | TLIDLC70-JDH |
Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C | 150/40° C |
Generator Model Number | UCI224E | UCI224F | UCI224F | UCI224E |
Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz) | 75/66/57.4 | 83/76/66 | 75/66/57.4 | 75/66/57.4 |
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 260 | 310 | 260 | 260 |
Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
Subtransient Reactance at Voltage Listed | 12.00% | 11.00% | 12.00% | 12.00% |
Line - Line Harmonic Maximum Total | 5.00% | 5.00% | 5.00% | 5.00% |