| Alternator Performance Data for TLIDLC60-JD |
| Model | TLIDLC60-JDA | TLIDLC60-JDB | TLIDLC60-JDD | TLIDLC60-JDH |
| Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C | 150/40° C |
| Generator Model Number | UCI224E | UCI224F | UCI224F | UCI224E |
| Generator kW at 130/105/80°C/40°C Ambient (480V, 60Hz) | 60/54.4/48 | 75/66/57.4 | 75/66/57.4 | 60/54.4/48 |
| SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 210 | 260 | 260 | 210 |
| Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
| Subtransient Reactance at Voltage Listed | 12.00% | 12.00% | 12.00% | 12.00% |
| Line - Line Harmonic Maximum Total | 5.00% | 5.00% | 5.00% | 5.00% |