Alternator Performance Data for TLIDLC450-D |
Model | TLIDLC450-DA | TLIDLC450-DB | TLIDLC450-DC | TLIDLC450-DH |
Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C | 150/40° C |
Generator Model Number | HCI544C | HCI544D | HCI544E | HCI544C |
Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz) | 475/430/376 | 515/470/412 | 600/540/475 | 475/430/376 |
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 1100 | 1300 | 1500 | 1100 |
Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
Subtransient Reactance at Voltage Listed | 11.00% | 10.00% | 10.00% | 11.00% |
Line - Line Harmonic Maximum Total | 5.00% | 5.00% | 5.00% | 5.00% |