| Alternator Performance Data for TLIDLC350-D |
| Model | TLIDLC350-DA | TLIDLC350-DB | TLIDLC350-DC | TLIDLC350-DH |
| Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C | 150/40° C |
| Generator Model Number | HCI444E | HCI444F | HCI544C | HCI444E |
| Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz) | 335/305/268 | 380/350/308 | 475/430/376 | 335/305/268 |
| SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 850 | 1200 | 1100 | 850 |
| Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
| Subtransient Reactance at Voltage Listed | 12.00% | 10.00% | 11.00% | 12.00% |
| Line - Line Harmonic Maximum Total | 5.00% | 5.00% | 5.00% | 5.00% |