Alternator Performance Data for TLIDLC300-D
ModelTLIDLC300-DATLIDLC300-DBTLIDLC300-DCTLIDLC300-DH
Temperature Rise By Resistance (Stand-By)150/40° C150/40° C150/40° C150/40° C
Generator Model NumberHCI444DHCI444EHCI444FHCI444D
Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz)300/272/236335/305/268380/350/308300/272/236
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz7308501200730
Maximum SKVA at 90% Sustained Voltage DipConsult Tele-LiteConsult Tele-LiteConsult Tele-LiteConsult Tele-Lite
Subtransient Reactance at Voltage Listed13.00%12.00%10.00%13.00%
Line - Line Harmonic Maximum Total5.00%5.00%5.00%5.00%