| Alternator Performance Data for TLIDLC30-JD |
| Model | TLIDLC30-JDA | TLIDLC30-JDB | TLIDLC30-JDC | TLIDLC30-JDH |
| Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C | 150/40° C |
| Generator Model Number | BCI184F | BCI184G | UCI224C | UCI224C |
| Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz) | 28/26/24 | 30/27.5/24.5 | 44/38.4/33.6 | 44/38.4/33.6 |
| SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 65 | 77 | 140 | 140 |
| Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
| Subtransient Reactance at Voltage Listed | 12.00% | 10.00% | 13.00% | 13.00% |
| Line - Line Harmonic Maximum Total | 5.00% | 5.00% | 5.00% | 5.00% |