Alternator Performance Data for TLIDLC275-D
ModelTLIDLC275-DATLIDLC275-DBTLIDLC275-DH
Temperature Rise By Resistance (Stand-By)150/40° C150/40° C150/40° C
Generator Model NumberHCI444DHCI444EHCI444D
Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz)300/272/236335/305/268300/272/236
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz730850730
Maximum SKVA at 90% Sustained Voltage DipConsult Tele-LiteConsult Tele-LiteConsult Tele-Lite
Subtransient Reactance at Voltage Listed13.00%12.00%13.00%
Line - Line Harmonic Maximum Total5.00%5.00%5.00%