Alternator Performance Data for TLIDLC275-D |
Model | TLIDLC275-DA | TLIDLC275-DB | TLIDLC275-DH |
Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C |
Generator Model Number | HCI444D | HCI444E | HCI444D |
Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz) | 300/272/236 | 335/305/268 | 300/272/236 |
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 730 | 850 | 730 |
Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
Subtransient Reactance at Voltage Listed | 13.00% | 12.00% | 13.00% |
Line - Line Harmonic Maximum Total | 5.00% | 5.00% | 5.00% |