| Alternator Performance Data for TLIDLC250-JD |
| Model | TLIDLC250-JDA | TLIDLC250-JDB | TLIDLC250-JDC | TLIDLC250-JDE |
| Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C | 150/40° C |
| Generator Model Number | UCD274J | HCI444C | HCI444D | HCI444F |
| Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz) | 240/220/194 | 250/225/198 | 300/272/236 | 380/350/308 |
| SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 680 | 700 | 850 | 1200 |
| Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
| Subtransient Reactance at Voltage Listed | 8.00% | 14.00% | 13.00% | 10.00% |
| Line - Line Harmonic Maximum Total | 5.00% | 5.00% | 5.00% | 5.00% |