Alternator Performance Data for TLIDLC200-JD |
Model | TLIDLC200-JDB | TLIDLC200-JDC | TLIDLC200-JDD | TLIDLC200-JDH |
Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C | 150/40° C |
Generator Model Number | UCI274H | UCI274J | UCI274J | UCI274H |
Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz) | 204/188/163 | 240/220/194 | 240/220/194 | 204/188/163 |
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 800 | 680 | 680 | 800 |
Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
Subtransient Reactance at Voltage Listed | 11.00% | 8.00% | 8.00% | 11.00% |
Line - Line Harmonic Maximum Total | 5.00% | 5.00% | 5.00% | 5.00% |