Alternator Performance Data for TLIDLC200-JD
ModelTLIDLC200-JDBTLIDLC200-JDCTLIDLC200-JDDTLIDLC200-JDH
Temperature Rise By Resistance (Stand-By)150/40° C150/40° C150/40° C150/40° C
Generator Model NumberUCI274HUCI274JUCI274JUCI274H
Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz)204/188/163240/220/194240/220/194204/188/163
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz800680680800
Maximum SKVA at 90% Sustained Voltage DipConsult Tele-LiteConsult Tele-LiteConsult Tele-LiteConsult Tele-Lite
Subtransient Reactance at Voltage Listed11.00%8.00%8.00%11.00%
Line - Line Harmonic Maximum Total5.00%5.00%5.00%5.00%