Alternator Performance Data for TLIDLC180-JD |
Model | TLIDLC180-JDB | TLIDLC180-JDC | TLIDLC180-JDE | TLIDLC180-JDH |
Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C | 150/40° C |
Generator Model Number | UCI274G | UCI274H | UCI274J | UCI274G |
Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz) | 180/165/140 | 240/220/194 | 240/220/194 | 180/165/140 |
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 650 | 800 | 650 | 650 |
Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
Subtransient Reactance at Voltage Listed | 12.00% | 11.00% | 8.00% | 12.00% |
Line - Line Harmonic Maximum Total | 5.00% | 5.00% | 5.00% | 5.00% |