Alternator Performance Data for TLIDLC1600-M
ModelTLIDLC1600-MBTLIDLC1600-MCTLIDLC1600-MH
Temperature Rise By Resistance (Stand-By)150/40° C150/40° C150/40° C
Generator Model NumberHCI734GHCI734HHCI734G
Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz)1825/1680/14002000/1840/15921825/1680/1400
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz540071005400
Maximum SKVA at 90% Sustained Voltage DipConsult Tele-LiteConsult Tele-LiteConsult Tele-Lite
Subtransient Reactance at Voltage Listed16.00%14.00%16.00%
Line - Line Harmonic Maximum Total5.00%5.00%5.00%