| Alternator Performance Data for TLIDLC1250-M |
| Model | TLIDLC1250-MB | TLIDLC1250-MC | TLIDLC1250-MH |
| Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C |
| Generator Model Number | HCI734E | HCI734F | HCI734E |
| Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz) | 1300/1200/1040 | 1500/1400/1216 | 1300/1200/1040 |
| SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 3800 | 4300 | 3800 |
| Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
| Subtransient Reactance at Voltage Listed | 17.00% | 16.00% | 17.00% |
| Line - Line Harmonic Maximum Total | 5.00% | 0.00% | 5.00% |