Alternator Performance Data for TLIDLC1025-M |
Model | TLIDLC1025-MA | TLIDLC1025-MB | TLIDLC1025-MC | TLIDLC1025-MH |
Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C | 150/40° C |
Generator Model Number | HCI634J | HCI634K | HCI734E | HCI634J |
Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz) | 1040/950/828 | 1150/1050/900 | 1300/1200/1040 | 1040/950/828 |
SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 3000 | 3800 | 3800 | 3000 |
Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
Subtransient Reactance at Voltage Listed | 16.00% | 15.00% | 17.00% | 16.00% |
Line - Line Harmonic Maximum Total | 5.00% | 5.00% | 5.00% | 5.00% |