| Alternator Performance Data for TLIDLC100-JD2 |
| Model | TLIDLC100-JD2A | TLIDLC100-JD2B | TLIDLC100-JD2D | TLIDLC100-JD2H |
| Temperature Rise By Resistance (Stand-By) | 150/40° C | 150/40° C | 150/40° C | 150/40° C |
| Generator Model Number | UCI274C | UCI274D | UCI274C | UCI274C |
| Generator kW at 125/105/80°C/40°C Ambient (480V, 60Hz) | 100/90/78 | 117/105/88 | 100/90/78 | 100/90/78 |
| SKVA Output with 30% Voltage Dip Maximum, 100% Recovery at 60 Hz | 345 | 420 | 345 | 345 |
| Maximum SKVA at 90% Sustained Voltage Dip | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite | Consult Tele-Lite |
| Subtransient Reactance at Voltage Listed | 13.00% | 13.00% | 13.00% | 13.00% |
| Line - Line Harmonic Maximum Total | 5.00% | 5.00% | 5.00% | 5.00% |